----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 30
6.11.- Additional screens when RELAY OUTPUTS (2 relays) are equipped
With these outputs the CVM-144...C2 can be set to deliver:
A.- Pulse every certain kWh or kvarh (ENERGY). You can define the
value corresponding to the energy consumed for generating a pulse (0.5 s long):
kWh / 1 pulse or kvarh / 1 pulse
B.- ALARM conditions: the parameter to be controlled, the maximum value,
the minimum value and the delay are user-definable for each relay output.
----------------------------------------------------------------------------------
On the CVM-144 screen following messages appear at this SET-UP option:
OUT 1 RELAY 1
CODE
00
Parameter No. (1)
Depending on the selected variable we will pass to a.- or b.- sections
In case that no parameter is wanted to be programmed set par. No. = 00.
Parameter Symbol
phase L1
Code Symbol
phase L2
Code Symbol
phase L3
Code
Single voltage V 1 01 V 2 06 V 3 11
Current A 1 02 A 2 07 A 3 12
Active power kW 1 03 kW 2 08 kW 3 13
Reactive power
Inductive/ Capacitive
kvarL 1
kvarC 1
04 kvarL 2
kvarC 2
09 kvarL 3
kvarC 3
14
Power factor PF 1 05 PF 2 10 PF 3 15
% THD V THD V1 25 THD V2 26 THD V3 27
% THD A THD A1 28 THD A2 29 THD A3 30