Figure 14: Quadrupole circuit breaker for the auxiliary power circuit.
5.- Connect the power supply of the OPTIM HYB capacitor bank, closing the general quadru-
pole switch inside the capacitor bank using its lever (ON position) and check that the CPU LED
and the RS485 COM 2 RX and TX LEDs light up immediately and ash at an approximate rate
of once per second.
This indicates the correct operation of the Computer HYB processor and correct communica-
tions between the Computer HYB and the CVM-MINI-RS485, respectively.
6.- Check that the CVM-MINI-RS485 (in the OPTIM HYB models that come equipped with it)
installed in the door of the capacitor bank lights up, and then program the primary value of the
current transformers that provide the measurement signal to the analyzer. Follow the steps
below for this programming:
A.- Access the MEASUREMENT Setup by pressing the SETUP key until the unit enters
into programming mode.
The screen shown in Figure 15 will appear on the display, which allows you to program
the voltage primary.
Note : This programming is not necessary for 3 x 400 V / 1 x 230 V networks.
set
Pr i U
000001
Figure 15: Programming of the voltage primary, CVM-MINI-RS485.
B.- Press the key until the screen shown in Figure 16 appears on the display, which
allows you to program the current transformer primary.
set
pr i a
00005
Figure 16: Programming of the current primary, CVM-MINI-RS485.
To enter or modify the current primary, press the
max
key repeatedly to increase the
23