6.3.7.- Unit conguration variables
The following functions are implemented for these variables:
Function 0x04: reading registers.
Function 0x10: Writing multiple registers.
NB: The programming values must be written in hexadecimal.
It is necessary to change the screen when a setup change is made for communi-
cations in order for the changes take effect in the display.
6.3.7.1.- Date and time
These parameters occupy 1 register each.
Table 30:Modbus memory map: Conguration variables (Date and Time).
Date and Time
Configuration variable Address Valid data window Default value
Year 283C 2013 to 2076 -
Month 283D 1 to 12 -
Day 283E 1 to 31 -
Time 283F 0 to 23 -
Minutes 2840 0 to 59 -
Seconds 2841 0 to 59 -
Note: The 6 registers must be written at once (as a group), otherwise it will respond with an
error.
6.3.7.2.- Time zone
These parameters occupy 1 register each.
Table 31:Modbus memory map: Conguration variables (time zone).
Local time conguration
Configuration variable Address Valid data window Default value
Conguration of local time 2A9E Table 32 0
Time 2A9F
0: Winter
1:Summer
0
Note: The 2 registers must be written at once (as a group), otherwise it will respond with an
error.
188
CVM-B100 - CVM-B150
Instruction Manual