CDP
Instruction Manual 55
Figure 71: Setup web site: Auxiliary load relays (Manual).
You can manually activate each relay by pressing the corresponding button for
each one.
If you select dynamic management of the loads (Figure 72), you have to program
the following parameters:
Figure 72: Setup web site: Auxiliary load relays (Dynamic).
• Max. modulation value: In this section you enter the maximum modulation
value and can add dynamic loads to the system below.
• Connection Order: Select how you are going to connect the relays: By pri-
ority or rotating
• 1st/2nd/3rd Priority: If you have selected priority connection, you will then
select the priority for each of the relays.
• Max. grid contribution: In this section you enter the value for maximum grid
contribution, which is the minimum value for deactivating loads.
• Reconnecting time: Minimum time to allow system stabilisation between:
- the activation of two loads.
- the deactivation of two loads.
- the deactivation of the last load and the activation of a new one.