6�- TECHNICAL FEATURES
AC Power supply
Rated voltage
100���520V~
Frequency 50���60Hz
Consumption 4���10VA
Installation category CATIII300V
Voltage measurement circuit
Rated voltage (Un) 230VP-N,400VP-P
Voltage measurement margin 20to300VP-N,35to520VP-P
Frequency measurement margin 45���65Hz
Input impedance 660kΩ
Minimum measurement voltage (Vstart) 20VP-N,35VP-P
Installation category CATIII300V
Current measurement circuit
Nominal current (In) ���/5Aor���/1A
Current measurement margin 1to120%In
Minimum measurement current (Istart) 50mA
Installation category CATIII300V
Leakage current measurement circuit
Bymeansofanearthleakagetransformerwitha ratioof500turns
Nominal current of the secondary 3mA
Current measurement margin 10mAto1�5A
Minimum measurement current (Istart) 10mA
Measurement accuracy UNE-EN 61557-12
Voltage measurement 0�5%±1digit
Current measurement 0�5%±1digit
Active power measurement 0�5%±2digits
Reactive power measurement 1%±2digits
Active energy measurement Class1
Reactive energy measurement Class2
Digital outputs
Model Computer SMART III FAST 6 Computer SMART III FAST 12
Quantity 6 2 6 2
Type OPTOMOS NPN OPTOMOS NPN
Maximum voltage 60VDC 24VDC 60VDC 24VDC
Maximum current 0�2A 50mA 0�2A 50mA
Relay outputs
Quantity 2(fan,alarm)
Maximum voltage, open contacts 1kV
Maximum current 1A
Maximum switching power 2500VA
Electrical life 30x10
3
cycles
Mechanical working life 5x10
6
cycles
103