Code Description
E08*
Voltage THD Alarm�TheVoltageTHDlevelsinsomeofthephasesarehigher
thanthoseconguredintheVoltageTHDalarm�
E09*
Current x I THD Alarm�TheIxITHDlevelsinsomeofthephasesarehigher
thanthoseconguredintheIxITHDalarm�(IxITHDreferstothemultiplication
ofthecurrentbytheITHDofthesamecurrent,see"5�23�- CURRENT x I THD
ALARM")
E10*
Temperature Alarm�Themeasuredtemperatureishigherthanthatcongured
intheTemperaturealarm�
E11 No Connection StatusduetoE08,E09 or E10
E12 Disconnection StatusduetoE08,E09 or E10
E13
Leakage Alarm�Theleakagecurrentishigherthanthatconguredinthe
LeakageCurrentalarm�
E14
Repeated Leakage Alarm�Leakageshavebeendetectedrepeatedlyinthe
system,
buttheyarenotcausedbyacapacitor
E15
Leakage in Capacitors Alarm�Leakageshavebeendetected,whichwere
causedbysomeofthecapacitors,andthisstageisdisabled�Thedisabled
capacitorswillstarttoblinkonthescreen�TheE13messagewillalsobedis-
played�
Inordertoenablethesecapacitorsagain,viewthecongurationoftheLeak-
agealarm�
E16
Leakage transformer detection Alarm�TheLeakagealarmhasbeenena-
bled,buttheunitdoesnotdetecttheconnectionoftheleakagecurrenttrans-
former
E17
Number of connections alarm�Thecongurednumberofoperationshas
beenexceeded(anycapacitor)
* Inthesealarms,twolevelshavebeencongured:
TheLo value: Whentheunitexceedsthisvaluefor30minutes,thecorrespondingalarmis
triggeredand,ifalarmE11 isenabled,theSMART III FASTunitentersNo Connection status
andactivates alarmE11
TheHI value : iftheunitexceedsthisvaluefor30seconds,thecorrespondingalarmis
triggeredand,ifalarmE12 isenabled,theSMART III FASTunitentersDisconnection status
andactivates alarmE12
IftheunitfallsbackundertheLo valuefor10minutes,itdeactivatesthealarmsandreturnstothe
normaloperatingstatus�
IntheNo Connectionstatus,theunitdoesnotconnectthestages,butalsodoesnotdisconnectthem
iftheoperationrequiresit�
IntheDisconnectionstatus,itdisconnectsthestagesanddoesnotallowthemtoconnect�
42