OutputassociatedwithAlarmE01 1170
0(No),
1(Alarmrelay),
2(Digitaloutput1)
2(Digitaloutput2)
0
OutputassociatedwithAlarmE02 1171 0
OutputassociatedwithAlarmE03 1172 0
OutputassociatedwithAlarmE04 1173 0
OutputassociatedwithAlarmE05 1174 0
OutputassociatedwithAlarmE06 1175 0
OutputassociatedwithAlarmE07 1176 0
OutputassociatedwithAlarmE08 1177 0
OutputassociatedwithAlarmE09 1179 0
OutputassociatedwithAlarmE10 1179 0
OutputassociatedwithAlarmE11 117A 0
OutputassociatedwithAlarmE12 117B 0
OutputassociatedwithAlarmE13 117C 0
OutputassociatedwithAlarmE14 117D 0
OutputassociatedwithAlarmE15 117E 0
OutputassociatedwithAlarmE16 117F 0
OutputassociatedwithAlarmE17 1180 0
C�-Deleting parameters
ParameterscanbedeletedusingFunction 05:writingarelay�
Table 37:Modbus memory map: deleting parameters
Deleting parameters
Action Address Value to be sent
Deletingmaximumvalues 200 FF
Deletingminimumvalues 210 FF
Deletingmaximumandminimumvalues 220 FF
Deletingenergies 230 FF
Deletingthestagesearchandstageenablingvaluesoftheleakagecurrent
alarm
240 FF
Deletingtheno�ofoperationsofalltherelays 250 FF
ResettingalarmsE14andE15 260 FF
Restoringthedefaultcongurationvalues 300 FF
4�9�4� EXAMPLE OF A MODBUS QUERY
Query:InstantaneousvalueoftheL1phasevoltage
Address
Func-
tion
Initial log No� of logs CRC
0A 04 0000 0002 70B0
Address: 0A,Peripheralnumber:10indecimal�
Function: 04,Readfunction�
Initial Log: 0000,logfromwhichtostartreading�
No� of logs: 0002,numberoflogstoberead�
CRC: 70B0,CRCcharacter�
68
Computer SMART III FAST
Instruction Manual
Kommentare zu diesen Handbüchern