Ifthevalueenteredislowerthantheminimumvalueorhigherthanthemaximumvalue,
thebacklightofthedisplayashesandthevalueenteredisreplacedwiththeminimumor
maximumvalue,orwiththelastvaluevalidated�
Pressthe keytoaccessthenextprogrammingstep�
Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,“5�27�-
SIMULATION SCREEN”�
5�23�-CURRENTxITHDALARM
Inthispointthethresholdsabovewhichthealarm
forthepercentageofthevalueofthecurrentx
ITHD(E09)isactivatedcanbeconfigured�
Thealarmmustbeenabled(“5�19�- ENABLING
ALARMS”
Theprogrammedvaluesareusefulforthe3
phaseswhichtheunitmeasures�
Pressthe
keytoentereditingmode�Itis
identifiedbythe symbolandtheblinkingof
thedigitstobemodified�
Thevaluetobeprogrammedinthisalarmcorrespondsdirectlytothevalueofthetotal
harmoniccurrenttobeconsideredasthesetpoint�For example: If you want to program a Lo
setpoint value when exceeding a harmonic current of 200 A measured by the regulator, program
00200 directly in this section.
Theparameterstobeconfiguredare:
TheLo value: whentheunitexceedsthisvaluefor30minutes,alarmE09 is
triggered,andifalarmE11 is enabled, the SMART III FASTunitentersNo Connection
statusandactivates alarmE11�
TheHI value: iftheunitexceedsthisvaluefor30seconds,alarmE09istriggered,
andifalarmE12isenabled,theSMART III FASTunitenterstheDisconnection status
andactivates alarmE12�
IftheunitfallsbackundertheLo valuefor10minutes,itdeactivatesthealarmsandreturns
tothenormaloperatingstatus�
IntheNo Connectionstatus,theunitdoesnotconnectthestages,butalsodoesnot
disconnectthemiftheoperationrequiresit�
IntheDisconnectionstatus,itdisconnectsallthestagesanddoesnotallowthemtoconnect�
The keyincreasesthedigitvalue�
97
Instruction Manual
Computer SMART III FAST