Table 33:Modbus memory map: programming variables (Table 19)
Alarm: Fan
Configuration variable Address Valid data margin Default value
Value 114C 0-80ºC 35
Enabled 114D 0(OFF),1(ON) 0
Table 34:Modbus memory map: programming variables (Table 20)
Alarm: Voltage
Configuration variable Address Valid data margin Default value
Overvoltagevalue 114E-114F 0-99999 440
NoVoltageValue 1150-1151 0-99999 360
Table 35:Modbus memory map: programming variables (Table 21)
No� of operations
Configuration variable Address Valid data margin Default value
No�ofoperations 1152-1153 1-99999 5000
Table 36:Modbus memory map: programming variables (Table 22)
Enabling alarms
Configuration variable Address Valid data margin Default value
EnableAlarmE01 1155
0(OFF),1(ON)
1
EnableAlarmE02 1156 1
EnableAlarmE03 1157 1
EnableAlarmE04 1158 1
EnableAlarmE05 1159 0
EnableAlarmE06 115A 0
EnableAlarmE07 115B 0
EnableAlarmE08 115C 0
EnableAlarmE09 115D 0
EnableAlarmE10 115E 0
EnableAlarmE11 115F 0
EnableAlarmE12 1160 0
EnableAlarmE13 1161 0
EnableAlarmE14 1162 0
EnableAlarmE15 1163 0
EnableAlarmE16 1164 0
EnableAlarmE17 1165 0
67