30
CVM
k
2
CONFIGURATION
Parameters that can be congured on this screen follow:
• PRIM. U.: Primary on the voltage transformers. If it does not exist,
program 1. The maximum congurable value is 999999.
• SEC. U.: Secondary on the voltage transformers. If it does not exist,
program 1. The maximum congurable value is a 3 digit number 999.
• PRIM. I.: Primary on the current transformer. The maximum congurable value is 30000.
• PRIM. In.: Primary on the current transformer for the neutral line. The maximum
congurable value is 30000.
The default value is 5. If it is desirable for the CVMk2 to show the neutral line
current that is calculated, congure 0.
• Sec. I.: Secondary on the current transformer. It is possible to program 5 or 1.
To store the modied parameters in memory, press SET and conrm with OK (F4). To exit without
saving changes press ESC (F3).
WARNING: The CVMk2 power calculation is limited according to the
following ratio:
(Prim V) x (Prim I) < 45.000.000
4.2. QUALITY
To access the power supply quality parameters conguration screen, position the cursor over
quality and press SET. Two options are provided in the quality menu, Quality and Events.
CVMk2 has no battery. When supply falls down the analyzer do not store electrical
parmeters and no quality events. Is very important to guarantee the supply of the
device from an interrupted source (Batery, SAI, ...)